Print

 

BurstIndicator

Burst Indicator
Type SVT 02

The cost efficient alarm SVT 02 is recommended for all standard applications in a temperature range from -30℃ to +220℃. The delivery is completely ready for installation and includes seals and connecting cables. It is of course fit for use for DIN, ANSI and JIS flanges – and can be configured with other seals depending on the application case as well.

Specifications
Temperature range -30 ℃ to +220 ℃
max amperage 50 mA
max resistance before bursting 20 Ω
Conductor path material Silver
Membrane PEEK
Seals Klingersil C 4400
Power supply cable Teflon coated, 2 m long
other sealing materials can be delivered upon request.
Model
SVT 02 STRIKO – VerfahrensTechnik Burst Indicatr 02
Advantages in the application
  • Quick identification of a malfunction
  • Simple assembly
  • Maintenance-free
  • Deliverable in nominal widths DN 25 to DN 600
  • In every system it can be combined with metal and graphite bursting seals, also with bursting discs from other manufacturers
  • Can be also used with bursting discs that can be attached without holder between the flanges.
  • Retrofitting is also possible thanks to low installation height (5mm)
  • the alarm is a separate component and independent of the bursting disc
  • Can also be used downstream of safety valves
  • Continuous temperature range from -30° to +220°
 
Note about ATEX

According to notification 3.42-10333/98-El of the National Metrology Institute (PTB) of 07/01/1998 the alarm represents, in terms of the ignition protection type own safety “i”, a so called simple electrical operating material, and is described in detail in Section 5.4 from EN 50020. Simple electrical operating materials must not be certified, if they meet the requirements from EN 50020 and Section 6.1.3.1.3 from DIN VDE 0165/1991-02 “Establishing an electrical system in explosive areas”. All STRIKO alarms meet these requirements.