D348D Ultrasonic Flowmeter

Multipath Ultrasonic Flowmeter

Applications and measurement

Water supply, circulation cooling water, sewage treatment and power-plant circulation water. Published examples include DN800 water supply and DN1000 cooling-water installations.

Multipath ultrasonic measurement for industrial and commercial applications, with insertion and spool-piece configurations. PICOFly time measurement reaches 10 picoseconds (0.01 nanosecond) resolution and a sampling rate up to 1000 times per second. Published spool-piece accuracy is ±0.2% and insertion accuracy ±0.5% of measured value.

About D348D

The D348D adopts Gentos PICOFly time measurement technology for high-response, high-accuracy ultrasonic measurement.

  • Low power consumption, high reliability, anti-jamming and broad applicability.
  • Clear, user-friendly menu selections.
  • Daily, monthly and yearly totalized flow.
  • Positive, negative and net totalizers with scale factor (span) and 7-digit display; totalizer pulse and frequency outputs transmitted through relay and open collector.
D348D transmitter with wetted insertion transducers

Application and Installation Guidance

Measurement location

Select a measurement site where the fluid flow profile is fully developed for highly accurate measurement.

Choose a pipe section that is always full of liquid, such as a vertical pipe with upward flow or a full horizontal pipe.

Provide at least the straight upstream and downstream lengths shown for the transducer installation.

Ensure the pipe surface temperature at the measuring point is within the transducer temperature limits.

Check the pipe interior carefully; where possible, choose a section free of excessive corrosion or scaling.

Channels and transducers

Published sensor choices: 2 channels for pipe sizes over DN150; 3 over DN300; 4 over DN400; and 6 over DN600.

W210 and W110 are wetted transducers, rated −40°C to +80°C. The dimension notes specify W210 for 150–1200 mm pipe and W110 for 150–3000 mm. Review these limits alongside the installation drawings.

Spool pieces

Carbon-steel spool and flange dimensions are shown below. DIN, JIS, EN and other pipe/flange standards are available with the customer's operating standard and drawing; pricing is revised accordingly. Large pipes and flanges also require the operating standard and drawing.

Include spool-piece requirements in your enquiry; the published ordering table does not define a separate spool-piece code.

Technical Data, Dimensions and Wiring

Performance specifications

Flow range
0.01–7 m/s (0.03–23 ft/s)
Accuracy
Spool piece: ±0.2% of measured value. Insertion: ±0.5% of measured value.
Repeatability
Spool piece: 0.07%. Insertion: 0.15%.
Pipe size
Spool piece: 100–3000 mm (4–120 in). Insertion: 100–5000 mm (4–200 in).

Function specifications

Analog output
4–20 mA; maximum load 750 Ω.
Pulse output
0–10 kHz, OCT.
Relay output
125 VAC at 1 A or 30 VDC at 2 A.
Communication
RS232 / RS485; Modbus Protocol.
Power supply
90–245 VAC, 48–63 Hz or 12–36 VDC.
Keypad
22 keys with tactile action: 16 (4 × 4) touch keys and 6 function keys.
Display
40 characters, 2 lines (20 × 2), alphanumeric backlit LCD.
Temperature
Transmitter: −10°C to 60°C (14°F to 140°F). Transducer: −40°C to 80°C (−40°F to 176°F).
Humidity
Up to 99% RH, non-condensing.
Installation
Wall mount.

Physical specifications

Transmitter
IP65. Hazardous rating printed in specifications: ExiaIIBT4.
Transducer
IP68; sealing design.
Transducer cable
Standard: 30 ft (9 m). Maximum: 344 ft (105 m).
W210
208 mm dimension; pipe size 150–1200 mm.
W110
287 mm dimension; pipe size 150–3000 mm.
Transmitter dimensions
230 × 280 × 110 mm; 35 mm cable-gland extension.

Configuration notes

Ordering output label
The ordering table prints RS-458; the specification and wiring diagram identify RS485.
Pipe-size limits
The general insertion range is 100–5000 mm; the transducer drawing specifies W210 at 150–1200 mm and W110 at 150–3000 mm. Confirm the selected transducer and installation for the pipe.
Flow range in ordering table
The ordering table prints 0.03–±23 ft/s (0.01–±7 m/s). It also lists ±0.5% accuracy at ±1.6 to ±16 ft/s.
Power supply labels
The wiring artwork labels DC 10–36 V; the specification and ordering table list 12–36 VDC.
Hazardous-area markings
The specification prints ExiaIIBT4; enclosure option 2 is labelled Exd II BT4 in the ordering table. Confirm the required classification.

Wiring Diagram

D348D original wiring diagram, with all labels retained

Transmitter Dimensions — mm

D348D original transmitter dimensions — mm, with all labels retained

Transducer Dimensions — mm

D348D original transducer dimensions — mm, with all labels retained

Flange Dimensions

Carbon-steel flange and section drawing labelled O, W, R, B, X, Y, f, ft and I
Carbon steel — dimensions in mm
NPSDNOverall Ø OBolt circle Ø WBolt hole Ø IHoles nFace Ø RRaised face fThickness ftThreaded / slip-on / socket welding YHub Ø XInside Ø B
4DN100230190.519.18157.2223.932135116.1
5DN125255215.922.38185.7223.935164143.8
6DN150280241.322.38215.9225.438192170.7
8DN200345298.522.38269.9228.643246221.5
10DN250405362.025.412323.8230.248305276.2
12DN300485431.825.412381.0231.854365327.0
14DN350535476.328.612412.8235.056400359.2
16DN400595539.828.616469.9236.662457410.5
18DN450635577.931.816533.4239.767505461.8
20DN500700635.031.820584.2242.971559513.1
24DN600815749.335.020692.2247.781663616.0

ASME B16.5-2009: page 64, Chart 4 — flange processing surface dimensions; page 71, Chart 7 — 150 Grade flange drillplate; page 73, Chart 8 — 150 Grade flange dimensions.

Spool Piece Dimensions

Carbon-steel spool piece and complete section showing length L, outer diameter OD, inner diameter ID and thickness n
Carbon steel — dimensions in mm, weights in kg
NPSDNLength LOuter Ø ODInner Ø IDThickness nFlange weight (kg)Spool piece weight (kg)
4DN100400114.30102.266.025.718.8
5DN125420141.30128.206.556.522.7
6DN150450168.30154.087.117.729.0
8DN200510219.10202.748.1812.246.5
10DN250580273.00254.469.2716.266.5
12DN300640323.80304.749.5325.097.2
14DN350680355.60336.549.5333.7122.5
16DN400740406.40387.349.5341.6151.8
18DN450780457.00437.949.5346.2173.9
20DN500860508.00488.949.5359.5219.9
24DN600980610.00590.949.5383.2303.4

ASME B36.10M-2004, page 5, Chart 1 — welded and rolled seamless steel tube dimensions and weight. For other standards or large pipes/flanges, provide the operating standard and drawing.

Transducer Installation Methods

D348D V and Z methods: complete profile, section and top views, with the published pipe-size ranges

Installation Site Selection

Minimum straight pipe lengths, expressed as multiples of pipe diameter D:

90° bend
10D upstream / 5D downstream
Tee
50D / 10D
Diffuser
30D / 5D
Reducer
10D / 5D
Valve
30D / 10D
Vertical pipe
10D / 5D
Pump
50D after the pump
Original straight-pipe installation diagrams: bend, tee, diffuser, reducer, valve, vertical pipe and pump

Spool Piece Production and Testing

Production

The manufacturer describes a 3000 m² pipeline processing plant covering stainless-steel plate cutting, reelpiping, welding, flange mating, polishing and pickling. Non-destructive testing is carried out throughout welding, with a material testing report to meet design requirements.

Original spool-piece production photograph

Third-party testing

Products can be tested by a third party according to customer requirements.

Original test report and third-party calibration photographs

Build your D348D ordering code

Example — Standard Model: D348D-1-1-2-W210-030

Multipath ultrasonic flowmeter, 4–20mA output, two-channel path wetted transducer with 9m cable.

Ordering information
Application and pipe details (optional)

Your ordering code

D348D-…-…-…-…-…

Request a quote